CONVERSION UNIT SELECTION


Luminaire safety class ---->

Safety Class I (metal)

Safety Class I (metal)

Safety Class I (metal)

Safety Class I (metal)

Safety Class II (plastic)

Safety Class II (plastic)

Safety Class II (plastic)

Safety Class II (plastic)

LED-Array:
Isolation type (1)--->

SELV

SELV

non SELV

non SELV

SELV

SELV

non SELV

non SELV


Accessibily (4) (5) --->

touchable LEDs (4)

non touchable LEDs (5)

non touchable LEDs (5)

non touchable LEDs (5)

touchable LEDs (4)

non touchable LEDs (5)

non touchable LEDs (5)

non touchable LEDs (5)

Rated working voltage U
of the LED-Array (2) --->

12Vdc < U
<55Vdc

20Vdc < U
<105Vdc

20Vdc < U
<130Vdc

100Vdc < U
<220Vdc

12Vdc < U
<55Vdc

20Vdc < U
<105Vdc

20Vdc < U
<130Vdc

100Vdc < U
<220Vdc



Mounting inside the luminaire

LEHF
LEHH
LELK
LELW
LELT

LELK
LELW
LELT

LEHF
LEHH
LEHZ

LEHF
LEHH
LEHZ
LELK
LELW
LELT

LELT

LELT

LELT


Mounting in an additional case
outside the luminaire

LEHF
LEHH
LELK
LELW
LELT

LELK
LELW
LELT

LEHF
LEHH
LEHZ

LEHF
LEHH
LEHZ
LELK
LELW
LELT

LEHF
LEHH
LELK
LELW
LELT

LELK
LELW
LELT

LEHF
LEHH
LEHZ

LEHF
LEHH
LEHZ
LELK
LELW
LELT

Mounting outside the luminaire without additional case

LELM

LELM

 

LELM

LELM

LELM

 

LELM

Suitable unit voltage type

55V

105V

130V

220V

55V

105V

130V

220V

Maximum output voltage of the converter unit with faulty LED-Array (3)


< 60Vdc


< 120Vdc


< 150Vdc


< 300Vdc


< 60Vdc


< 120Vdc


< 150Vdc


< 300Vdc

NOTES

(1) PELV and FELV LED-Arrays (i.e. LED-Arrays connected to earth) are not usable because of high-frequency mains reinjection current under emergency, which cannot be filtered by the conversion kit (the EMC-standard cannot be complied to).

(2) Measurement with LED-array switched on (measurement on the LED-array or value given on the LED-converter).

(3) Measurement with LED-array switched on and either faulty or disconnected LED-Array.

(4) The LEDs are touchable if the luminaire cover can be removed without having to use a tool.

(5) The LEDs are non touchable if the luminaire cover cannot be removed without having to use a tool.

CASES

Emergency Lighting Unit type

Case type

Case material

Case dimension
(L x W x H) in mm

Hole spacing in mm

Notes

LEHF

F

Metal

210 x 31.5 x 21.5

205.5

No strain relief. Battery connection through connector on unit.

LEHH

H

Metal

180 x 40 x 28

175.5

No strain relief. Battery connection on cable.

LEHZ

Z

Metal

126 x 60.5 x 29

121

No strain relief. Battery connection through connector on unit.

LELK

K

Metal

150 x 30.2 x 22.1

142

No strain relief. Battery connection through connector on unit.

LELT

T

PC

177.2 x 30 x 21.5

169.2

No strain relief. Battery connection through connector on unit.

LELY

Y

PC

108 x 37.4 x 22

no holes

under development

LELM

M

PC

292 x 81 x 41

no holes

Case for battery and electronic module with strain relief for cables.

LELW (autumn 2018)

W

Metal

234 x 45 x 11.5

226

No strain relief. Battery connection through connector on unit.